Comparison Chart

The following table lists the specifications of the Davicom Remote Monitoring and Control Systems. Select the unit that best suits your needs.

 


Options
DV-Micro
DV-Mini
DV-208
DV-216
Analog Inputs 8 8 8 16
Digital Inputs 8 16 16 32
60W SPDT Relays 8 8 16 32
Analog Input Ranges 0 to +5 VDC (¹) ±2.5, ±10, ±20V (²) ±2.5, ±10, ±20V (²) ±2.5, ±10, ±20V (²)
4-20mA Analog Inputs NO YES YES YES
Audio Detection on Analog Inputs NO YES High Precision True-RMS Option High Precision True-RMS Option
Auxiliary Serial Ports (for reach-through to external equipment) 0 1 (³) 4 (³) 8 (³)
RS-232 Port (front panel) NO YES YES YES
Ethernet Ports 1 2 2 2
Built-in SNMP Client NO V1, V2C, V3 V1, V2C, V3 V1, V2C, V3
Built-in SNMP Manager NO 96 GETs, 96 SETs et 96 traps 96 GETs, 96 SETs et 96 traps 96 GETs, 96 SETs et 96 traps
Smartphone App NO Android, iOS Android, iOS Android, iOS
On-Board Real Time Clock (RTC) Standard Precision High Precision TCXO High Precision TCXO High Precision TCXO
Audio Inputs for monitoring over Dial-Up (300Hz - 3KHz) 1 2 4 8
Audio Inputs for monitoring over IP 0 2 4 8
Front Panel Buttons Local Pause/Local Pause/Local Pause/Local
Rack Space 1 RU, half width 1 RU 2 RU 2 RU
Dimensions (W x H x D) 8 1/2 X 1 3/4 X 12 in21.6 X 4.4 X 30.5 cm (W x H x D) 19 X 1 3/4 X 12 in48.3 X 4.4 X 30.5 cm (W x H x D) 19 X 3 1/2 X 12 in48.3 X 8.9 X 30.5 cm (W x H x D) 19 X 3 1/2 X 12 in48.3 X 8.9 X 30.5 cm
Weight 4 lbs (1.8 kg) 6 lbs (2.7 kg) 7 lbs (3.2 kg) 8 lbs (3.6 kg)

(¹) Input range expandable to 5V, 15V, 30V and 60V with optional MIOBU-1 screw terminal board.

(²) Differential inputs.

(³) Up to 8 optional USB-to-serial adapters can be added for tunneling to other devices.