Home  | Français | Careers | See our Ads & Articles | News Archives | About Us | Search:    
 
   






Refer this site to a friend
 
 
SENSOR, LINE FREQUENCY



Product ordering code: LFS-1 or LFS-2
 
The Line Frequency Sensor provides an analog output which is proportional to the frequency of the input source. It is normally used to monitor power-line frequency variations in Alternating Current (AC) Systems.
 
Polynomial equation linearization coefficients for the Frequency Sensor:
 
For readings in Hz, enter the ABC coefficients given below:
 
LFS-1 MAC2, MiniMAC2, MicroMAC: A=0; B=2; C=55;
 
LFS-2 MAC2, MiniMAC2, MicroMAC: A=0; B=2; C=45;
 

ELECTRICAL SPECIFICATIONS
Model LFS-1 LFS-2
Input Frequency
55 - 65 Hz
45 - 55 Hz
Voltage Range
95 - 135 VAC
190 - 270 VAC
Supply Voltage
Self-powered
Self-powered
Output Voltage 0 - 5 VDC 0 - 5 VDC

 
MECHANICAL SPECIFICATIONS
Dimensions

5.25 x 2.5 x 4.38 in.(W x D x H)

13.64 x 6.35 x 11.13 cm

Weight
1.3 lbs (0.59 kg)